Panic hardware door latching assembly incorporating a device which releases the latch upon application of a force in the direction of exit travel.
Exit door panic hardware requirements.
A force of 15 pounds applied to the touch pad or cross bar must release the latch.
The actuating portion of the panic device must be at least half the width of the door.
An exit door must be unlocked.
Exit devices are required by building code and local fire departments for many public buildings.
Other requirements for panic hardware include.
Codes to know for panic hardware where panic hardware is required the actuating portion of the device touchpad or crossbar must be at least half the.
When panic hardware.
Panic hardware is an exit device which is tested for u.
An applied force of 15 pounds should be enough to release the latch.
A device such as a panic bar that locks only from the outside is permitted on exit discharge doors.
Panic hardware used on balanced doors must be touchpad type and the touchpad must not extend more than half.
It should not require more than 15 pounds of force to unlatch it.
Buildings will not pass inspection if they are not up to the life safety code with door hardware.
Panic hardware and fire exit hardware are two different types of exit devices and the proper selection is determined by code requirements.
However some codes have recently.
Force required to operate.
Above all equip doors with panic hardware and fire exit hardware.
Because of its durability and ease of use panic hardware is also commonly installed in places where it isn t required by code.
The actuating portion of the exit device needs to be at least half the width of the actual door.
Some codes and standards require panic hardware to operate.
No more than 15lbs.
Current codes require panic hardware to be mounted between 34 inches and 48 inches above the floor.
2 hand activated door opening hardware shall be centered between 30 inches and 44 inches above the floor.
You should never add a chain lock padlock an extra deadbolt or any electric latches or components that would delay the opening of an egress panic hardware equipped door.
The maximum unlatching force shall not exceed 15 pounds.
Hardware consisting of bars that extend to at least half of the width of the door leaf.
1 panic hardware shall cause the door latch to release when a force not exceeding 15 pounds is applied to the releasing device in the direction of exit traffic.
Where panic hardware is required the actuating portion of the device touchpad or crossbar must be at least half the.